Specifications
92
Building Technologies 007004_k_en_--
Fire Safety & Security Products 16.04.2009
Ambient conditions Permitted ambient temperature Depending on parameter set
Storage temperature -30 … +75 °C
Air humidity ≤95 % rel.
Protection categories according to
EN 60529/IEC 60529:
z Base FDB221/FDB222 IP43
z Base attachment FDB291 with base
FDB221/FDB222
IP43
z Base attachment humid FDB293 with
base FDB221/FDB222
IP54
Electromagnetic compatibility:
z 1 MHz ... 2 GHz 50 V/m
Static response temperature:
z Parameter set BR and BS 78 … 82 ℃
z Parameter set A1R and A1S 58 … 62 ℃
Mechanical data Colour ∼RAL 9010 pure white
Standards Standards EN 54-5, EN 54-17
VdS approvals:
z FDT221 G204020
z FDT241 G204019
LPCB approvals:
z FDT221 126aa/02
z FDT241 126aa/01
FM approvals:
z FDT221 3029351
z FDT241 3029351
Certificates:
z FDT221 0786-CPD-20003
z FDT241 0786-CPD-20004
CE conformity mark Yes
QA Standards Siemens Standard SN 36350

Table of Contents