EasyManua.ls Logo

Siemens LDS 6 - Pin Assignment of LDS 6

Siemens LDS 6
102 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation Guidelines
3.3 Electrical Connections
LDS 6
34 Operating Instructions, 01/2009, A5E00295894-05
3.3.4 Pin Assignment of LDS 6
The signal connection is carried out by using two DSUB connectors for each channel – one
15 pins and one 25 pins.
4
5
12
13
14
15
1
2
3
6
7
8
9
10
11
12
13
7
8
9
10
11
4
5
17
18
19
1
2
3
6
16
21
14
20
15
22
23
24
25
GND
Contact loading
max. 24 V/1 A, AC/DC
The relay is de-energized in
the shown contact position
Floating via opto isolator
"0" = 0 V (0 to 4.5 V)
"1" = 24 V (13 to 33 V)
Binary inputs 1 to 4-N
Binary input 1-P
Binary input 2-P
Binary input 3-P
Binary input 4-P
GND
GND
Relay 1
Relay 2
Relay 3
Relay 4
Relay 5
Relay 6
GND
Connector SUB-D 25F
Temperature correction
Temperature correction
Pressure correction
Pressure correction
Analog outputs:
floating
(also to one another),
R
L
750 Ω
Non-floating
analog inputs
GND
Analog output 2-P
GND
NC
GND
Analog output 1-N
Analog output 1-P
Analog output 2-N
Analog input 2-P
Analog input 2-N
Analog input 1-P
Analog input 1-N
Binary input 6-P
Binary input 5-P
Binary inputs 5 to 6-N
GND
GND
GND
Connector SUB-D 15F
GND
Component 2
(if present)
Component 1
Floating via opto isolator
"0" = 0 V (0 to 4.5 V)
"1" = 24 V (13 to 33 V)
Figure 3-3 Pin assignment for I/O connections

Table of Contents