LME Series Technical Instructions
Document No. LME-1000
SCC Inc. Page 11 Appendix A
Honeywell Modutrol IV with the LME75 (continued)
11. Output X2-09.1 is energized in phase 10 to drive the mod motor to low fire. Since the
mod motor is already at the low fire position, the low fire proving switch is closed, and
actuator feedback input X2-09.4 is energized.
12. The LME75 transitions to standby, displayed as “OFF” on the LME75 and AZL23.