Building Technologies Basic Documentation LMV27... CC1P7541en
26 Parameter level 17.12.2018
Air
Fuel
Curvepoints
Angle
Bild 216e/1109
Figure 82: Setting the curvepoints
Note
Curvepoints P2 to P8 are automatically calculated as a straight line between P1 and
P9.
Example 1 = gas modulating
P0, P1 and P9 are set as described: Curvepoint Value 1
fuel
Value 2
air
P0
30.0 22.0
P1
32.0 24.0
P9
80.0 90.0
P2 through P8 have automatically been
calculated:
Curvepoint Value 1
fuel
Value 2
air
P2
38.0 32.3
P3
44.0 40.5
P4
50.0 48.8
P5
56.0 57
P6
62.0 65.3
P7
68.0 73.5
P8
74.0 81.8