165/219
Building Technologies Basic Documentation LMV27... CC1P7541en
26 Parameter level 17.12.2018
Starting the warm settings
F
or
A
and
or
P
Vh
mi n
s%
Bild 118/0707
Ignition position P0 can only be set when
symbol
or is no longer highlighted.
For fuel, keep
F
depressed, for air
.
Press
or to adjust the value.
When symbol
or is no longer
highlighted, the next curvepoint P1 can be
selected with
.
F
or
A
and
or
P
V
h
mi n
s%
Bild 123/0707
Low-flame position P1 can only be set when
symbol
or is no longer highlighted.
The value will be adopted from P0.
For fuel, keep
F
depressed, for air
.
Press
or to adjust the value.
When symbol
or is no longer
highlighted, the next curvepoint P2 can be
selected with
.
To the next curvepoint
Back to the previous
curvepoint
P
Vh
mi n
s%
Bild 124/0707
When changing from P1 to P2 for the first time,
curvepoints P2…P8 will automatically be
calculated and saved.
CALC appears for a short moment.