177/219
Building Technologies Basic Documentation LMV27... CC1P7541en
26 Parameter level 17.12.2018
A
and
or
P
Vh
mi n
s%
Bild 150/0707
Low-fire position P1 can be set only when
symbol
or is no longer highlighted.
Set stage 1 P1.
Fuel valve V1 is switched on.
Keep
depressed.
Press
or to adjust the value.
When symbol
or is no longer
highlighted, the next curvepoint P2on can
be selected with
.
To the next curvepoint
A
and
or
P
Vh
mi n
s
%
Bild 151/0707
Curvepoint P2on can be set only when
symbol
or is no longer highlighted.
Set switch-on point stage 2 P2.
Fuel valve V2 is still off.
Keep
depressed.
Adjust the value with
or .
When symbol
or is no longer
highlighted, the next curvepoint P2_d can
be selected with
.
To the next curvepoint
Back to the previous
curvepoint.
A
and
or
P
Vh
mi n
s%
Bild 152/0707
Curvepoint P2_d can be set only when
symbol
or is no longer highlighted.
Fuel valve V2 is still off and the LMV27 remains
at curvepoint P2on. Presetting of operating
stage P2 with no travel, aimed at cutting the
operating time if there is shortage of air.
Keep
depressed.
Press
or to adjust the value.
When symbol
or is no longer
highlighted, the next curvepoint P2 can be
selected with
.