MD-P1 Point Map by Application Number with Point Map Comparison
Supported P1 Applications
Siemens Industry, Inc.
32
09/30/2019
125-201
P1
Point
Point
Type
Type
No.
P1 Name
Units
Default
Value
Detail
Slope
for P1
Apps
Intercept
for P1
Apps
MD-P1
Series**
Apps
2771-
2777
MD-P1
Series*
*
App
2779
DEM1000*
Apps 710-
716
DEM2000*
Apps 717-
723
- returns new value every min., will
compare and post to min/max
registers
11
LAI
3
POWER FACTOR
PF
0
System Total Displacement Power
Factor
0.01
0
12
LAI
3
CURRENT
A
0
System Average Current for All
Phases
0.01 for
2771,
2773,
2774
0.02 for
2775.
2776
0.05 for
2772,
2777
1.0 for
2779
0
13
LAI
3
VOLTAGE LL
V
0
Average Line to Line Voltage for all
Phases
0.1
0
14
LAI
3
VOLTAGE LN
V
0
Average Line to Neutral Voltage for
all Phases
0.1
0
15
LAI
3
APPARENT PWR
kVA
0
System Total Apparent Power
= unsigned value of ABS(kVA
L1)+ABS(kVA L2)+ABS(kVA L3)
0.1
0
16
LAI
3
REACTIVE PWR
kVAR
0
System Total Reactive Power
= unsigned value of ABS(kVAR
L1)+ABS(kVAR L2)+ABS(kVAR L3)
0.1
0
17
LAI
3
VOLTAGE A B
V
0
Individual Phase L1 to Phase L2
Voltage
0.1
0
18
LAI
3
VOLTAGE B C
V
0
Individual Phase L2 to Phase L3
Voltage
0.1
0
19
LAI
3
VOLTAGE A C
V
0
Individual Phase L1 to Phase L3
Voltage
0.1
0
20
LAO
4
OVRD TIME
0
P1 Override Time
1
0