Loading...
MD-P1 Point Map by Application Number with Point Map Comparison
Supported P1 Applications
1
Siemens Industry, Inc.
33
9/30/2019
125-201
P1
Point
Point
Type
Type
No.
P1 Name
Units
Default
Value
Detail
Slope
for P1
Apps
Intercept
for P1
Apps
MD-P1
Series**
Apps
2771-
2777
MD-P1
Series*
*
App
2779
DEM1000*
Apps 710-
716
DEM2000*
Apps 717-
723
21
LAI
3
VOLTAGE A N
V
0
Individual Phase L1 to Neutral
Voltage
0.1
0
22
LAI
3
VOLTAGE B N
V
0
Individual Phase L2 to Neutral
Voltage
0.1
0
23
LAI
3
VOLTAGE C N
V
0
Individual Phase L3 to Neutral
Voltage
0.1
0
24
LAI
3
CURRENT A
A
0
Individual Phase L1 Current
0.01 for
2771,
2773,
2774
0.02 for
2775.
2776
0.05 for
2772,
2777
1.0 for
2779
0
25
LAI
3
CURRENT B
A
0
Individual Phase L2 Current
26
LAI
3
CURRENT C
A
0
Individual Phase L3 Current
27
LAI
3
KW AVG POS
kW
0
System Average Positive Power
Draw
= positive kW System / (Time since
Reset/3600sec/Hour (resettable)
0.1
0
28
LAI
3
KW AVG NEG
kW
0
System Average Negative Power
Draw
= negative kW System / (Time since
Reset/3600sec/Hour (resettable)
0.1
0
29
LDO
2
DAY.NGT
0
0 = DAY (off text = "DAY"); 1 =
NIGHT (on text = "NIGHT")
1
0
30
LAI
3
KW MAX
kW
0
System Maximum Instantaneous
Power Draw
= system highest 500ms power
draw value since reset (resettable)
0.1
0
31
LAI
3
KW MAX POS
kW
0
System Maximum Instantaneous
Positive Power Draw
0.1
0