MD-P1 Point Map by Application Number with Point Map Comparison
Supported P1 Applications
Siemens Industry, Inc.
34
09/30/2019
125-201
P1
Point
Point
Type
Type
No.
P1 Name
Units
Default
Value
Detail
Slope
for P1
Apps
Intercept
for P1
Apps
MD-P1
Series**
Apps
2771-
2777
MD-P1
Series*
*
App
2779
DEM1000*
Apps 710-
716
DEM2000*
Apps 717-
723
= system max 500ms positive power
draw value since reset (resettable)
32
LAI
3
KW MAX NEG
kW
0
System Maximum Instantaneous
Negative Power Draw
= system max 500ms negative
power draw value since reset
(resettable)
0.1
0
33
LAI
3
KW MIN
kW
0
System Minimum Instantaneous
Power Draw
= system lowest 500ms power draw
value since reset (resettable)
0.1
0
34
LAI
3
KW MIN POS
kW
0
System Minimum Instantaneous
Positive Power Draw
= system min 500ms positive power
draw value since reset (resettable)
0.1
0
35
LAI
3
KW MIN NEG
kW
0
System Minimum Instantaneous
Negative Power Draw
= system min 500ms negative
power draw value since reset
(resettable)
0.1
0
36
LAI
3
KW A
kW
0
Individual instantaneous Phase L1
True Power
0.1
0
37
LAI
3
KW B
kW
0
Individual instantaneous Phase L2
True Power
0.1
0
38
LAI
3
KW C
kW
0
Individual instantaneous Phase L3
True Power
0.1
0
39
LAI
3
KVAR A
kVAR
0
Individual instantaneous Phase L1
Reactive Power
0.1
0
40
LAI
3
KVAR B
kVAR
0
Individual instantaneous Phase L2
Reactive Power
0.1
0
41
LAI
3
KVAR C
kVAR
0
Individual instantaneous Phase L3
Reactive Power
0.1
0