MD-P1 Point Map by Application Number with Point Map Comparison
Supported P1 Applications
1
Siemens Industry, Inc.
35
9/30/2019
125-201
P1
Point
Point
Type
Type
No.
P1 Name
Units
Default
Value
Detail
Slope
for P1
Apps
Intercept
for P1
Apps
MD-P1
Series**
Apps
2771-
2777
MD-P1
Series*
*
App
2779
DEM1000*
Apps 710-
716
DEM2000*
Apps 717-
723
42
LAI
3
KVAR DEM MAX
kVAR
0
System Maximum Instantaneous
Reactive Power Demand
= maximum demand value read
since startup or reset of demand
register
0.1
0
43
LAI
3
KVAR DEM NOW
kVAR
0
System Average Reactive Power
Demand
returns new value every minute, will
compare and post to min/max
registers
0.1
0
44
LAI
3
KVARH NET LO
kVARh
0
System Total Net Reactive Energy
LSW
= unsigned value of ABS(kVARh
L1)+ABS(kVARh L2)+ABS(kVARh
L3)
1
0
45
LAI
3
KVARH NET HI
kVARh
0
System Total Net Reactive Energy
MSW
= unsigned value of ABS(kVARh
L1)+ABS(kVARh L2)+ABS(kVARh
L3)
1
0
46
LAI
3
KVAR SYS NET
kVAR
0
System Net Total Reactive Power
= signed net value of ABS(kVAR
L1)+ABS(kVAR L2)+ABS(kVAR L3)
0.1
0
47
LAI
3
KWH NT P LO
kWh
0
System Net Lowest Positive True
Energy
1
0
48
LAI
3
KWH NT P HI
kWh
0
System Net Highest Positive True
Energy
1
0
49
LAI
3
KWH NT N LO
kWh
0
System Net Lowest Negative True
Energy
1
0
50
LAI
3
KWH NT N HI
kWh
0
System Net Highest Negative True
Energy
1
0
51
LAI
3
KW NET POS
kW
0
System Net Positive Power
0.1
0
52
LAI
3
KW NET NEG
kW
0
System Net Negative Power
0.1
0