Issue 04/02 2 Installation
MICROMASTER 410 Operating Instructions
6SE6400-5EA00-0BP0
23
30 mm
100 mm
100 mm
30 mm
Figure 2-5 Clearance distances for mounting the inverter
For side mounting and UL compliance the ambient temperature should be no
greater than 40 ºC. The maximum output current of the 750 W inverter is 3.2 A.
Table 2-5 Dimensions and Torques of MM410
Overall Dimensions
Frame
Size
Height Width Depth
Fixing Method
Tightening Torque
of fixings
AA
150 mm
(5.91”)
69 mm
(2.72”)
118 mm
(4.65”)
2 x M4 Bolts*
2 x M4 Nuts*
2 x M4 Washers*
or
Connecting to DIN rail**
2.5 Nm
with washers fitted
AB
150 mm
(5.91”)
69 mm
(2.72”)
138 mm
(5.43”)
2 x M4 Bolts*
2 x M4 Nuts*
2 x M4 Washers*
or
Connecting to DIN rail**
2.5 Nm
with washers fitted
* Not supplied with the inverter.
** The DIN rail mounting kit is an optional extra which must be ordered separately. For details see
Section 2.7.2 on page 25.