Issue 04/02 3  Commissioning
MICROMASTER 410    Operating Instructions
6SE6400-5EA00-0BP0
41
Motor data for parameterization
50 Hz
230/400V
0.61 0.35 A
Cos
j
0.81
Cos
j
0.81
65%
0.12kW
2800 / min
3_Mot
IEC 56
IM B3
Nr. ED510 3053
IP54 Rot KL 16
60 Hz 440V Y
0.34A
0.14 kW
3310 /min
S.F. 1.15
12.022
I.CI.F
P0308 P0310 P0304
P0309 P0305 P0311 P0307
D/
Y
Figure 3-7 Typical Motor Rating Plate Example
NOTE
Ø  P0308 & P0309 are only visible if P0003 = 3. Only one of the parameters is
shown depending on the settings of P0100.
Ø  P0307 indicates kW or hp depending upon the setting of P0100. For detailed
information, please see the Parameter List.
Ø  Changing motor parameters is not possible unless P0010 = 1.
Ø  Ensure that the motor is configured correctly to the inverter (star/delta connection).
3.2.4.3  Reset to Factory default
To reset all parameters to the factory default settings; the following parameters
should be set as follows (the operator panel option is required):
1.  Set P0010 = 30
2.  Set P0970 = 1
NOTE
The reset process can take up to 3 minutes to complete.