Issue 04/02 3 Commissioning
MICROMASTER 410 Operating Instructions
6SE6400-5EA00-0BP0
39
NOTE
In some cases - when changing parameter values - the display on the Operator
Panel shows
. This means the inverter is busy with tasks of higher priority.
Changing single digits in Parameter values
For changing the parameter value rapidly, the single digits of the display can be
changed by performing the following actions:
Ensure you are in the parameter value changing level (see "Changing parameters
with Operator Panel").
1. Press
(function button), which causes the right hand digit to blink.
2. Change the value of this digit by pressing
/ .
3. Press
(function button) again causes the next digit to blink.
4. Perform steps 2 to 4 until the required value is displayed.
5. Press the
to leave the parameter value changing level.
NOTE
The function button may also be used to acknowledge a fault condition
3.2.4.2 Quick commissioning (P0010=1)
It is important that parameter P0010 is used for commissioning and P0003 is used
to select the number of parameters to be accessed. This parameter allows a group
of parameters to be selected that will enable quick commissioning. Parameters
such as Motor settings and Ramp settings are included.
At the end of the quick commissioning sequence, P3900 should be selected,
which, when set to 1, will carry out the necessary motor calculations and clear all
other parameters (not included in P0010=1) to the default settings. This will only
happen in the Quick Commissioning mode.