ECO REFERENCE MANUAL
13-12
Automatic restart after fault 0 - 1
[0]
Automatic restart after fault:
0 = Disabled
1 = The inverter will attempt to restart up to
5 times after a fault. If the fault is not
cleared after the 5th attempt, the
inverter will remain in the fault state.
The display flashes during this
condition.
WARNING:
While waiting to re-start, the display will
flash. This means that a start is pending and
may happen at any time. Fault codes can be
observed in P930.
Skip frequency bandwidth
(Hz)
0.0 - 10.0
[2.0]
Frequencies set by P014, P027, P028 and
P029 that are within +/- the value of P019 of
all skip frequencies are suppressed.