EasyManua.ls Logo

Siemens Midimaster Eco - Page 103

Siemens Midimaster Eco
183 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ECO REFERENCE MANUAL
13-13
Parameter Function Range
[default]
Description / Notes
Minimum analogue
frequency (Hz)
0 - 150.0
[0.0]
Frequency corresponding to the lowest
analogue input value, i.e.0 V/0 mA or 2 V/4
mA, determined by P023 and the settings of
the DIP selector switches 1, 2 and 3 (
see
the DIP Selector Switches figure in this
section).
This can be set to a higher value
than P022 to give an inverse relationship
between analogue input and frequency
output
(see diagram in P022)
.
Maximum analogue
frequency (Hz)
0 - 150.0
[50.0]
(60)North
America
Frequency corresponding to the highest
analogue input value, i.e.10 V or 20 mA,
determined by P023 and the setting of the
DIP selector switches 1, 2 and 3 (
see the
DIP Selector Switches figure in this section).
This can be set to a lower value than P021
to give an inverse relationship between
analogue input and frequency output. i.e.
f
V/ I
P021
P021
P022
P022
Note: The output frequency is limited by
values entered for P012/P013.
Analogue input 1 type 0 - 2
[0]
Sets analogue input type for analogue input
1, in conjunction with the settings of the DIP
selector switches 1, 2 and 3 (See
see the
DIP Selector Switches figure in this section)
0 = 0 V to 10 V/ 0 to 20 mA Unipolar input
1 = 2 V to 10 V/ 4 to 20 mA Unipolar input
2 = 2 V to 10 V/ 4 to 20 mA Unipolar input
with controlled start/stop when using
analogue input control.

Table of Contents

Other manuals for Siemens Midimaster Eco

Related product manuals