ECO REFERENCE MANUAL
13-14
Parameter Function Range
[default]
Description / Notes
Analogue output 1 0 - 105
[0]
This provides a method of scaling the
analogue output 1 in accordance with the
following table:
Use range 0 - 5 if minimum output value = 0
mA.
Use range 100 - 105 if minimum output value
= 4 mA
P025= Selection Analogue Output Range Limits
0/4 mA 20 mA
0/100
Output frequency 0 Hz Output frequency
(P013)
1/101
Frequency setpoint 0 Hz Frequency setpoint
(P013)
2/102
Motor current 0 A Max. overload current
(P083 x P086/100)
3/103
DC-link voltage 0 V 1023 Vdc
4/104
Motor torque -250% +250%
(100% = P085/P082 x
9.55Nm)
5/105
Motor RPM 0 Nominal motor RPM
(P082)
Analogue output 2
(MIDIMASTER Eco only)
0 - 105
[2]
This provides a method of scaling the
analogue output 2 in accordance with the
table shown in P025.
Skip frequency 2 (Hz) 0 - 150.0
[0.0]
See P014.
Skip frequency 3 (Hz) 0 - 150.0
[0.0]
See P014.
Skip frequency 4 (Hz) 0 - 150.0
[0]
See P014.
Fixed frequency1 (Hz) 0 -
150.00
[5.00]
Valid if P006 = 2 and P055 = 6 or 18
Fixed frequency 2 (Hz) 0 -
150.00
[10.00]
Valid if P006 = 2 and P054 = 6 or 18
Fixed frequency 3 (Hz) 0 -
150.00
[15.00]
Valid if P006 = 2 and P053 = 6 or 18
Fixed frequency 4 (Hz) 0 -
150.00
[20.00]
Valid if P006 = 2 and P052 = 6 or 18.
Fixed frequency 5 (Hz) 0 -
150.00
[25.0]
Valid if P006 = 2 and P051 = 6 or 18..