ECO REFERENCE MANUAL
13-26
Parameter Function Range
[default]
Description / Notes
Enable/disable RUN button 0 - 1
[1]
0 = RUN button disabled
1 = RUN button enabled (only possible if
P007 = 1)
Enable/disable and
buttons
0 - 1
[1]
0 = and buttons disabled
1 = and buttons enabled (only possible
if P007 = 1)
This applies for frequency adjustment only.
The buttons can still be used to change
parameter values.
Fan switch-off delay time
(seconds) (MMV only)
0 - 600
[120]
Time taken for the fan to switch off following
an OFF command.
Frequency setpoint (Hz) 0.0-
150.0[-]
Motor current (A) 0.0 -
300.0
[-]
Motor torque (% nominal
torque)
0 - 250
[-]
Read-only parameters. These are copies of
the values stored in P001 but can be
accessed directly via the serial link.
DC link voltage (V) 0 - 1000
[-]
Motor RPM 0 - 9999
[-]
Output voltage (V) 0 - 1000
[-]
Most recent fault code 0 - 255
[-]
Read only. The last recorded fault code (see
‘Fault Codes’) is stored in this parameter. It
is cleared when the inverter is reset.
This is a copy of the code stored in P930.
Most recent fault code -1 0 - 255
[-]
Read only. This parameter stores the last
recorded fault code prior to that stored in
P140/P930.
Most recent fault code -2 0 - 255
[-]
Read only. This parameter stores the last
recorded fault code prior to that stored in
P141.
Most recent fault code -3 0 - 255
[-]
Read only. This parameter stores the last
recorded fault code prior to that stored in
P142.