ECO REFERENCE MANUAL
13-9
Parameter Function Range
[default]
Description / Notes
Display mode 0 - 8
[0]
Display selection:
0 = Output frequency (Hz)
1 = Frequency setpoint (i.e. speed at which
inverter is
set to run) (Hz)
2 = Motor current (A)
3 = DC-link voltage (V)
4 = Motor torque (% nominal)
5 = Motor speed (rpm)
6 = USS serial bus status (see section 9.2)
7 = PID Feedback signal (%)
8 = Output voltage (V)
The display can be scaled via P010.
Ramp-up time 0-150.0
[20]
This is the time taken for the motor to
accelerate from standstill to the maximum
frequency. The maximum frequency is set
by parameter P013. Setting the ramp-up
time too short can cause the inverter to trip
(Fault code F002 = overcurrent).
)UHTXHQF\
I
PD[
+]
7LPH
5DPS XS
WLPH