EasyManua.ls Logo

Siemens MindConnect Nano - Firewall Settings

Siemens MindConnect Nano
131 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
To make sure a configuration works for your setup it needs to be monitored over a
longer period of time.
System Test results
The following tables show how long it takes to read a data item from one of the devices. These
are not fixed values but an indication of how the devices would react.
MindConnect NANO:
Type
MS per data point read:
Min
MS per data point read:
Mid
MS per data point read:
Max
S7 300 1,13 1,74 3,08
S7 1500 0,37 1,60 3,89
S7 1200 3,50 5,18 7,50
S7 ET200S CPU 0,89 2,09 3,71
OPC UA @
PC¹
2,38 6,64 8,53
OPC UA@ PLC 2,66 3,27 4,69
¹ OPC UA @ PC always depends on the hardware.
Read of a string data point you have to multiply the time with 2,5 per data point
All devices are around 75% full
8.9 Firewall Settings
It is recommended to use a firewall between the Internet and the MindConnect Nano, this is also
recommended for communication to the automation network.
In the direction to Automation Network a firewall supporting NAPT (in case of DMZ, see section
List of abbreviations”) or supporting the Ghost-Mode is required. Siemens offers many types
of Firewalls for fulfilling these requirements.
Appendix
8.9 Firewall Settings
MindConnect Nano
System Manual 7/2023119

Table of Contents

Other manuals for Siemens MindConnect Nano

Related product manuals