System Messages
C-2
MP270 Equipment Manual
Release 01/99
Note
System messages are displayed in the language selected in the configuration.
Procedure in the case of “internal errors”
Adopt the following procedure for all system messages referring to “internal errors”:
1. Switch the operating unit off, set the PLC to the STOP status and then start up
both units again.
2. Download the configuration again and then restart the PLC and operating unit.
3. If the fault occurs again, please contact your nearest Siemens representative.
When doing so, please quote the number of the error that has occurred and any
tags referred to in the message.
System message parameters
The system messages may contain parameters which are not decoded for the user
but which are relevant in respect of the cause of an error since they provide a
reference to the source code from ProTool/Pro Runtime. These parameters are
issued according to the text “Error code:”
Number Effect/Cause Remedy
10000 The print job could not be started or was terminated
for an unknown reason.
The printer is incorrectly configured.
Or: There are no rights for a network printer available.
Configure the printer again.
Initiate the assignment of rights for
a network printer.
10001 No printer has been installed or no standard printer
configured.
Install a printer and/or mark one as
standard printer.
10002 The intermediate buffer for printing graphics is full. Up
to two graphics can be buffered.
Do not issue print jobs so quickly in
succession.
10003 Graphics can be buffered again.
10004 The intermediate buffer for printing lines in text mode
(e.g. messages) is full. Up to 1000 lines can be
buffered.
Do not issue print jobs so quickly in
succession.
10005 Lines of text can be buffered again.
20010 A fault has occurred in the script line specified.
Execution of the script function was, therefore,
terminated.
In this case, it is advisable to check any previous
system messages too.
Select the specified script line in
the configuration.
Check tags, whether the types
used are permissible.
Check Functions, whether the
number and types of parameter
are correct.