System Messages
C-10
MP270 Equipment Manual
Release 01/99
RemedyEffect/CauseNumber
190101 The area pointer is not updated because it is not
possible to map the PLC type in the area pointer type.
Parameter type and no.: See message 190100
–
190102 The area pointer is updated following an error status
after the cause of the last error state has been
eliminated (return to normal operation).
Parameter type and no.: See message 190100
–
200000 Coordination is not executed because the address
configured in the PLC does not exist/has not been set
up.
Change the address or set up the
address in the PLC.
200001 Coordination is not executed because the address
configured in the PLC cannot be written.
Change the address or set up the
address in the PLC in an area
which can be written.
200002 Coordination is not executed at present because the
address format of the area pointer does not match the
internal storage format.
– (Internal error)
200003 Coordination can be executed again because the last
error status has been eliminated (return to normal
operation).
–
200004 It is possible that coordination is not executed. –
200005 No more data is read or written.
This can have various causes:
– The cable is defective.
– The PLC does not respond, is defective, etc.
– The system is overloaded.
Check that the cable is connected
and the PLC is in order.
Reboot the system if the system
message is displayed
continuously.
210000 Jobs are not processed because the address
configured in the PLC does not exist/has not been set
up.
Change the address or set up the
address in the PLC.
210001 Jobs are not processed because the address
configured in the PLC cannot be written to/read from.
Change the address or set up the
address in the PLC in an area
which can be written to/read from.
210002 Jobs are not executed because the address format of
the area pointer does not match the internal storage
format.
– (Internal error)
210003 The job mailbox is processed again because the last
error status has been eliminated (return to normal
operation).
–
210004 It is possible that the job mailbox is not processed. –
210005 A PLC job was triggered by an impermissible number. Check the PLC program.
210006 A fault occurred while attempting to execute the PLC
job. The PLC job is, therefore, not executed.
Observe the subsequent/previous system message, if
appropriate.
Check the parameter types in the
PLC job.
Compile the configuration again.