EasyManua.ls Logo

Siemens OCM III - BS-3680 Flumes and Weirs (P3=1-7)

Siemens OCM III
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
BS-3680 Rectangular Flume, P3 = 1
‘U’ parameters required * ‘U’ parameters calculated **
U0 = approach width B U4 = Cv
U1 = throat width b U5 = Cd
U2 = hump height p U6 = A
U3 = throat length L
*obtain from manufacturer’s specifications.
**
calculated by OCM-3. May be viewed by accessing ‘U’ parameter.
Reference
ABSOLUTE CALCULATION, P4 = 0
¤
For flows that can be calculated by the equation:
q = (2/3)
1.5
x g
0.5
x Cv x Cs x Cd x B x h
1.5
where : q = flow rate Cv = velocity coefficient
b = throat width Cs = shape coefficient
g = gravitational acceleration Cd = discharge coefficient
h = head
RATIOMETRIC CALCULATION, P4 = 1
¤
For flows that can be calculated by the equation:
q = q
cal
x Cd/Cd
cal
x Cv/Cv
cal
x (h/h
cal
)
1.5
where : q = flow rate
q
cal
= flow rate at maximum head
h = head
h
cal
= maximum head
Cv = velocity coefficient
Cv
cal
= velocity coefficient for maximum head
Cd = discharge coefficient for head
Cd
cal
= discharge coefficient for maximum head
¤
Refer to Operation \ Flow Calculation.