EasyManua.ls Logo

Siemens OCM III - Bs-3680 Finite Crest Weir, P3 = 5

Siemens OCM III
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
BS-3680 FINITE CREST WEIR, P3 = 5
‘U’ parameters required * ‘U’ parameters calculated **
U0 = crest width b U3 = C
U1 = crest height p U4 = Cp
U2 = crest length L
*
obtain from manufacturer’s specifications.
**
calculated by OCM-3. May be viewed by accessing ‘U’ parameter.
Reference
ABSOLUTE CALCULATION, P4 = 0
¤
For flows that can be calculated by the equation:
q = (2/3)
1.5
x g
0.5
x C x Cp x b x h
1.5
where : q = flow rate C = a function of h and L
g = gravitational acceleration
b = crest width Cp = a correction factor as a function
h = head of h and p applied to C
RATIOMETRIC CALCULATION, P4 = 1
¤
For flows that can be calculated by the equation:
q = q
cal
x C/C
cal
x Cp/Cp
cal
x (h/h
cal
)
1.5
where : q = flow rate
q
cal
= flow rate at maximum head
h = head
h
cal
= maximum head
C = discharge coefficient for head
C
cal
= discharge coefficient for maximum head
Cp = correction factor for C
Cp
cal
= correction factor for C
cal
¤
Refer to Operation \ Flow Calculation.
7ML19985AB01 OCM III 66

Table of Contents