EasyManuals Logo

Siemens PAD-5 Series User Manual

Siemens PAD-5 Series
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #35 background imageLoading...
Page #35 background image
Model PAD-5
1
Technical Data
Siemens Industry, Inc.
A6V101030358_en--_c
Smart Infrastructure
Operating Temperature
Temperature Range
0 49C
NAC circuit
Plug strip
X300, X400
Voltage
DC 24 V
Special Application for strobe loads
Regulated for non-pulsing loads
Standby operating current
Max. 10 mA
Active operating current
3 A (for a class A circuit or per class B circuit)
Regulated Current Rating
0.3A
NAC Circuit Configured as
a Input Shorting Device
Voltage
DC 24V
Current
< 10 mA
Line Impedance
Max. circuit resistance
1.6 Ω per wire (3.2 Ω max. loop)
Supervised for
Open circuit
Short circuit
Ground fault
Design
Short-circuit protection
Voltage surge protection
Power limited
AUX output
Plug strip
X800
Voltage
16-33 VDC "Special Application"
Current
Max. 3 A
Design
Short-circuit protection
Voltage surge protection
Power limited
NAC follower input
Plug strip
X600
Voltage
DC 24 V filtered
Current
Max. 12 mA
Design
Voltage surge protection

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens PAD-5 Series and is the answer not in the manual?

Siemens PAD-5 Series Specifications

General IconGeneral
BrandSiemens
ModelPAD-5 Series
CategoryComputer Hardware
LanguageEnglish

Related product manuals