Fail-Safe Modules
7.5 4/8 F-DI DC24V PROFIsafe Digital Electronic Module
ET 200S Distributed I/O System - Fail-Safe Modules
Installation and Operating Manual, 08/2008, A5E00103686-07
121
Wiring Diagram for Application 2.2 – Connecting Two Single-Channel Sensors to Two Channels
Two single-channel sensors are connected via two channels to two inputs of the F-module
for each process signal (1oo2 evaluation). The sensors can also be connected to an external
sensor supply.
)',
/ 0 ', ', ', ', ', ', ', ', 9V 9V
/ 0
6
6
6
6
30(
Figure 7-25 Wiring diagram EM 4/8 F-DI DC24V - two 1-channel sensors connected via two
channels, internal sensor supply
WARNING
To achieve SIL3/Category 3/PLe using this wiring, you must use a suitably qualified sensor.
Assignable Parameters for Application 2.2
Set the "sensor evaluation" to "1oo2 evaluation" at the corresponding input, and "2-channel
equivalent" at the "Type of sensor interconnection" parameter. Disable the "short-circuit test"
parameter.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens PM-E F pm DC24V PROFIsafe and is the answer not in the manual?

Siemens PM-E F pm DC24V PROFIsafe Specifications

General IconGeneral
BrandSiemens
ModelPM-E F pm DC24V PROFIsafe
CategoryControl Unit
LanguageEnglish

Related product manuals