Fail-Safe Modules   
7.3 PM-E F pp DC24V PROFIsafe power module 
  ET 200S Distributed I/O System - Fail-Safe Modules 
94  Installation and Operating Manual, 08/2008, A5E00103686-07 
Technical Specifications 
Electrical isolation 
 
•  Between output and backplane bus 
Yes 
•  Between output and power supply 
No 
•  Between output/power supply and shield 
Yes 
Permissible potential difference between   
•  shield and ET 200S bus connection 
75 VDC/60 VAC 
•  Shield and I/O (DOs, P1/P2 buses) 
75 VDC/60 VAC 
•  ET 200S bus connection and I/O (DOs, P1/P2 
buses) 
250 VAC 
Isolation in the series tested with   
•  Shield and ET 200S bus connection 
500 VDC/1 min or 600 VDC/1 s 
•  Shield and I/O (DOs, P1/P2 buses) 
500 VDC/1 min or 600 VDC/1 s 
•  ET 200S bus connection and I/O (DOs, P1/P2 
buses) 
1500 VAC/1 min or 2545 VDC/1 s 
Isolation in the type test tested with   
•  Shield and ET 200S bus connection 
350 VAC/1 min 
•  Shield and I/O (DOs, P1/P2 buses) 
350 VAC/1 min 
•  ET 200S bus connection and I/O (DOs, P1/P2 
buses) 
2830 VAC/1 min 
•  Surge voltage test between ET 200S bus 
connection and I/O (DOs, P1/P2 buses) 
6000 VDC/5 positive and 5 negative pulses 
Current consumption   
•  From backplane bus 
28 mA, maximum 
•  From load voltage L+ (without load) 
100 mA, typical 
Power dissipation of the module  4 W, typical 
Status, Interrupts, Diagnostics 
Status display 
•  Green LED per channel 
•  Green LED for the load voltage 
Diagnostic functions   
•  Group fault display 
Red LED (SF) 
•  Diagnostic information can be displayed 
Possible 
Data for Selecting an Actuator for the Relay Output* 
Switching capacity and service life of contacts 
(voltage 24 VDC) 
 
•  Mechanical endurance (without load) 
Current  Number of switching cycles (typ.) 
  0 A  10 million 
•  For resistive load 
Current  Number of switching cycles (typ.) 
10 A  0.23 million 
8 A  0.3 million 
6 A  0.38 million 
 
4 A  0.5 million