Siemens Standard application AHU CE1P3977en_02
Building Technologies Detail pages: Inputs and outputs 01.02.2010
Parameter Range Function
Contact Function
NO
NC
Changes input from Normal open to Normal closed:
Normal open (logical 1 on input = TRUE in the
program).
Normal closed (logical 0 on input = TRUE in the
program).
Value selector
Hardware
Comm
And.
Or.
PreferedHW
PrefComm
Select valid input value for the application:
Value on hardware input.
Value from communications.
The input is 1, if the value on the hardware input
and the value from communications = 1. Alarm
triggers (if enabled), if one of the two values is in-
valid.
The input is 1, if the value on the hardware input
or the value from communications = 1. Alarm
triggers (if enabled), if one of the two values is in-
valid.
Value on hardware input has priority. The value
from communications assumed if invalid. Alarm
triggers (if enabled), if both values are invalid.
Value from communications has priority. The
value from hardware input assumed if invalid.
Alarm triggers (if enabled), if both values are in-
valid.
6.6.3 Special information
Read: Levels 4 and 2.
Write: Not writable.
Parameter Range Function
Value selector
Hardware
Comm
And
Or
PreferedHW
PrefComm
Displays valid input value for the application:
Value on hardware input.
Value from communications.
The input is 1, if the value on the hardware input
and the value from communications = 1. Alarm
triggers (if enabled), if one of the two values is
invalid.
The input is 1, if the value on the hardware input
or the value from communications = 1. Alarm
triggers (if enabled), if one of the two values is
invalid.
Value on hardware input has priority. The value
from communications assumed if invalid. Alarm
triggers (if enabled), if both values are invalid.
Value from communications has priority. The
value from hardware input assumed if invalid.
Alarm triggers (if enabled), if both values are in-
valid.
Value HW Text abhängig von der Present value for hardware.
Access level
Parameter
Basis Document Siemens Climatix Control System
BDCX.100820.01GB
Page 108