Siemens Standard application AHU CE1P3977en_02
Building Technologies Detail pages: Inputs and outputs 01.02.2010
Parameter Range Function
Hardware.
Value comm Text abhängig von der
Hardware.
Present value from communications.
Reliability (Basis
Controller)
OK.
Other
Process Error
Config Error
Reliability state for hardware.
Calibration lacking. Controller must be returned
to the factory.
Internal fault.
Input not configured.
Reliability (Extension
Modul POL 955)
OK.
Other
Reliability state for hardware.
Calibration lacking. Controller must be returned
to the factory; internal fault or input not config-
ured.
Reliability comm OK.
Fault
Present reliability of value from communications.
Disable OffNormal
Passive
Active
The OffNormal alarm is disabled. Example: An
alarm is not triggered if alarm input true:
Alarm is triggered.
Alarm is not triggered.
Enable Value
Passive
Active
Displays enable of software input within the appli-
cation:
Input is disabled.
Input is enabled.
ToOffNormal Day of week, dd.mm.yyyy
hh:mm:ss
Date and time the last off normal alarm occurred.
ToFault Day of week, dd.mm.yyyy
hh:mm:ss
Data and time last fault alarm (Reliability <> 0) oc-
curred.
ToNormal Day of week, dd.mm.yyyy
hh:mm:ss
Date and time last alarm was reset.
Communication infos
Comm OK
????
Information on the communication status for ele-
ments.
No error.
Function not yet available.
Basis Document Siemens Climatix Control System
BDCX.100820.01GB
Page 109