The device won't accept the confirmation ID Check to make sure the confirmation ID being entered
is correct and try again.
The Device Not Configured message is
displayed on the LCD
Change any parameter in the device configuration or
load a user configuration via Reydisp Manager 2.
Error Indications
If the 7SR5 device is outside normal operating mode, this is shown by a Device Healthy indication. By default
this indication is prerouted to LED 1 and Binary Output 3.
Relay failure will be indicated by the Protection Healthy LED being off.
When a device error occurs, an error message on the LCD display will read SAD RELAY CALLED and this
means, the device is not ready for operation.
The relay will enter a locked-out mode. While in this mode it will disable operation of all LED’s and Binary
Outputs.
[sc_7SR5_SadRelayCalled, 1, --_--]
Figure 8-4 Sad Relay Called Display
Manually Changing IP Address of Reyrolle Adapter
In order to manually change the IP address of the Reyrolle Adapter the user should start by opening the
Windows Settings window (shortcut Windows Key + I).
8.2.2
8.2.3
Device Maintenance
8.2 Error Search and Correction
120 Reyrolle 7SR5, Operating, Manual