The device should be out of service and disconnected from the power system.
Browse to the device homepage of the device via a direct connection to the USB port or over an ethernet
connection to one of the rear ethernet ports of the device.
For the device front USB port use
https://192.168.2.1/upload to navigate directly and procced to the page.
For the rear ethernet port, it must be configured and the IP address used.
Use the Choose file option to navigate to the security patch .pck file downloaded from the website and
select Update.
i
i
NOTE
If the maintenance password is active a prompt window will request that it is entered before continuing.
[sc_7SR5_SecurityUpdate, 1, --_--]
Figure 8-18 Reydisp Manager 2 Security Update
i
i
NOTE
The user configuration files and data storage files will not be erased during a security patch update.
Device Maintenance
8.4 Update Firmware and Configuration
Reyrolle 7SR5, Operating, Manual 131
C53000-B7040-C013-1, Edition 05.2021