Device Data
Auxiliary Voltage V
aux
Rated auxiliary voltage
– Direct voltage DC 24 V to 250 V
– Alternating voltage AC 110 V to 230 V/45 Hz to 65 Hz
Permissible voltage range
– Direct voltage 19 V to 300 V
– Alternating voltage 92 V to 286 V
Power consumption
– Direct voltage Max. 2.2 W
– Alternating voltage Max. 6.5 VA
Current consumption
– Direct voltage Max. 120 mA
– Alternating voltage Max. 60 mA
Operating state display 1 green LED (Power On)
Fuses
Soldered in place T2.0 A/125 V
Replaceable T1.6 A/250 V/F1
Protection class III
Structural Variant
Housing
Metal (industrial housing)
Dimensions See the dimensional drawings at A.2 Dimensions
Weight About 450 g
Degree of protection according to EN 60529:
– Housing IP 41; metal
– Terminals IP 20
Safety
As per DIN EN 61010 Part 1, overvoltage category
III (AC 3.7 kVA/DC 5.2 kV)
Degree of pollution 2
Fire-resistance rating as per UL 94 V0
5.1
Technical Data
5.1 Device Data
34 Accessories, RS232 Optical Fiber Converter 7XV5652-0CA00, Manual
C53000-G9050-C606-1, Edition 03.2020