RUGGEDCOM RUGGEDCOM RSG2488
Installation Guide
Chapter 4
Technical Specifications
Power Supply Specifications 35
Technical Specifications
The following sections provide important technical specifications related to the device and available modules:
• Section 4.1, “Power Supply Specifications”
• Section 4.2, “Failsafe Relay Specifications”
• Section 4.3, “Copper Ethernet Port Specifications”
• Section 4.4, “Fiber Optic Ethernet Port Specifications”
• Section 4.5, “GPS Antenna Specifications”
• Section 4.6, “PTP Specifications”
• Section 4.7, “Supported Networking Standards”
• Section 4.8, “Operating Environment”
• Section 4.9, “Mechanical Specifications”
Section 4.1
Power Supply Specifications
NOTE
Use the internal fuse rating to determine the size of the external circuit breaker/fuse.
Input Range
Power
Supply Type
Terminal
Block Type
Min Max
Internal
Fuse Rating
Maximum Power
Consumption
Maximum
Cable Length
a
24 VDC (Single) 13 VDC 36 VDC 10 A 62 W 9.4 m (30.8 ft)
48 VDC (Single)
Screw
38 VDC 72 VDC 5 A 59 W 44.9 m (167 ft)
98 VDC 300 VDC
High Voltage
AC/DC
Screw/Pluggable
88 VAC 264 VAC
3.15 A 66 W —
a
Based on #16 AWG wiring.
Section 4.2
Failsafe Relay Specifications
IMPORTANT!
The alarm switching voltage must be greater than the Safety Extra Low-Voltage (SELV) to meet safety
requirements.