Technical specifications
6.7 Technical specifications for terminal modules
SIMATIC TOP connect for S7-1500 and ET200MP
Manual,
63
Table 6- 15 Technical specifications for terminal module TPRo
Terminal module TPRo with relays for outputs
6ES7924-0BD20-0Bx0
Operating voltage for coil 24 V DC 19 - 28.8 V
Input circuit Reverse polarity protection and freewheeling
Single contact, 1 NO contact
Switching capacity (resistive load)
Recommended minimum load ≥ 1 mA
6
Electrical
5 x 10
4
switching cycles at 230 V AC/4 A/ cos φ =
1, 6 x per minute
Inductive loads To protect the relay contacts, inductive loads
must be dampened externally with an effective
protective circuit. No measures are provided for
Connection to SIMATIC fitted for
16-pin IDC connector with fitted strain relief
Mounting position Any
Clearances and creepage distances IEC 60664-1, IEC61131-2,
CSA C22.2 No 142 UL 508, VDE 0160,
overvoltage category II,
pollution degree 2
Dimensions (W x H x D) in mm
6ES7924-0BG20-0Bx0 Approx. 100 x 76 x 60