S7-300 Automation System, Hardware and Installation: CPU 312IFM - 318-2 DP
A5E00203919-01
7-15
The two rows of the shielding contact element allow you install a maximum of
4 shielding terminals.
CPU
PS
1
1
22
3
Figure 7-6 Shielding contact element underneath two signal modules
7KHGLDJUDPLOOXVWUDWHVXQGHUQXPEHU
 Bracket of shielding contact element
 Edge of mounting bracket, where the shield connection terminal(s) must rest
 Shielding terminals
7HUPLQDWLQJFDEOHV
Only one or two shielded cables may be clamped per shielding terminal. The cable
is clamped in at the stripped cable shielding.
1. First, strip the cable shield to a length of at least 20 mm.
2. Now clamp in the stripped cable shield underneath the shielding terminal. Push
the shielding terminal towards the module and feed the cable through
underneath the clamp.