S7-300 Automation System, Hardware and Installation: CPU 312IFM - 318-2 DP
12-10 A5E00203919-01
1RWHWKHIROORZLQJSRLQWVRQIUDPHZDOOPRXQWLQJ
When mounting on varnished or anodized metal parts, use special contact
washers or remove the insulating layers.
Provide a large-surface and low-impedance metal-to-metal connection for
fastening the shielding/protective protective ground bar.
Always touch-protect live mains conductors.
The figure below shows an example of EMC compatible wall-mounting of an S7.
CPU
PS
Figure 12-3 Example of EMC compatible wall-mounting