0DLQWHQDQFH
S7-300 Automation System, Hardware and Installation: CPU 312IFM - 318-2 DP
10-2 A5E00203919-01
:KLFK&38VDOORZPHWREDFNXSWKHRSHUDWLQJV\VWHP"
You can back-up the operating system as of the following CPU versions:
&38 2UGHU1R )LUPZDUH 5HTXLUHG0&00&
313 from 6ES7313-1AD03-
0AB0
V 1.0.0 or later MC 1 MB
314 from 6ES7314-1AEx4-
0AB0
V 1.0.0 or later MC 1 MB
314 IFM from 6ES7314-5AE10-
0AB0
V 1.1.0 or later MC 2 MB
315 from 6ES7315-1AF03-
0AB0
V 1.0.0 or later MC 1 MB
315-2 DP from 6ES7315-2AFx3-
0AB0
V 1.0.0 or later MC 2 MB
316-2 DP from 6ES73136-2AG00-
0AB0
V 1.0.0 or later MC 2 MB
1RWH
A back-up of the operating system is not possible with CPU 318-2 DP.
%DFNXSRIWKHRSHUDWLQJV\VWHPRQPHPRU\FDUG
How to back up the operating system:
Table 10-1 Backup of the operating system on MC
6WHS $FWLRQUHTXLUHG &385HVSRQVH
1. Insert a new memory card into the
CPU
The CPU requests memory reset
2. Turn the mode selector switch to
MRES position and hold it there.
-
3. POWER OFF / POWER ON. Hold
the mode selector switch in MRES
position until ...
... the STOP, RUN and FRCE LEDs start
flashing.
4. Mode selector switch to STOP
position.
-
5. Mode selector switch briefly to
MRES position, then let it return to
STOP.
The CPU starts backing up the
operating system to the MC.
All LEDs are lit during the back-up.
When backup is complete, the
STOP-LED flashes. The CPU is
requesting a memory reset.