&RPPLVVLRQLQJ
S7-300 Automation System, Hardware and Installation: CPU 312IFM - 318-2 DP
9-8 A5E00203919-01
,QVHUWLQJDQGUHPRYLQJDPHPRU\FDUG)(3520LQ32:(52))0RGH
If you remove a memory card in POWER OFF mode and insert another memory
card with identical contents, the following happens after POWER ON:
&38EXIIHUHG &38V,)0WR'3
The CPU 318-2 goes into STOP mode and
requests memory reset.
The CPU switches to the mode it was in
prior to POWER OFF, that is, RUN or
STOP.
&RPPLVVLRQLQJWKHPRGXOHV
&RQQHFWLQJWKH3*
5HTXLUHPHQW
The programming device must be equipped with an integrated MPI interface or an
MPI card in order to connect it to the MPI interface of your CPU.
&URVVUHIHUHQFH
For information on possible cable lengths refer to the Chapter &RQILJXULQJ&DEOH
/HQJWKV.
&RQQHFWLQJD3*WRDQ6
1. Connect the programming device (PG) to the MPI interface of your CPU by
means of a preassembled PG cable .
Alternatively, you can produce the connecting leads with PROFIBUS cable and bus
connectors yourself (refer to Chapter :LULQJ&RQQHFWLQJ%XV&RQQHFWRUV).
SF
BUSF
DC5V
FRCE
RUN
STOP
SIEMENS
PG
CPUPS
SM
MPI
1
Figure 9-3 Connecting a PG to an S7-300