&RPPLVVLRQLQJ
S7-300 Automation System, Hardware and Installation: CPU 312IFM - 318-2 DP
A5E00203919-01
9-33
352),%86$GGUHVV
With CPU 31x-2 DP, do not set  as PROFIBUS address.
 'LUHFW'DWD([FKDQJH
5HTXLUHPHQW
In 67(3 V 5.x or later, you can configure "Direct data exchange" for PROFIBUS
nodes. CPUs with a DP interface can take part in direct data exchange as senders
and receivers.
'HILQLWLRQ
"Direct data exchange" is a special communication relationship between
PROFIBUS-DP nodes.
Characteristic of direct data exchange is that PROFIBUS DP nodes "listen" on the
bus for data a DP slave returns to its DP master. This mechanism allows "Listening
stations" (receivers) direct access to modified input data of remote DP slaves.
$GGUHVV$UHDV
In your 67(3 configuration of the relevant peripheral input addresses, specify
which address area of the receiving node is to receive data requested from the
sending node.
The following types of DP-CPU are possible:
DP slave sending station
receiving station, as DP slave or DP master, or as CPU not integrated in a
master system.