S7-300 Automation System, Hardware and Installation: CPU 312IFM - 318-2 DP
8-6 A5E00203919-01
$QH[DPSOHIRUDQDORJPRGXOHV
The example in the figure below shows you which default channel addresses are
obtained if an analog module is inserted in slot 4. As you can see, the input and
output channels of an analog I/O module are addressed starting at the same
address, namely the module start address.
Slot number 3 has not been assigned since there is no interface module in the
example.
Slot
number
2
4
Inputs
:
:
Outputs
1
:
:
SF
BUSF
DC5V
FRCE
RUN
STOP
SIEMENS
CPU
PS
SM
SM (analog module)
Channel 0: address 256
Channel 1: address 258
Channel 0: address 256
Channel 1: address 258
Figure 8-4 I/O addresses of an analog module in Slot 4
$GGUHVVLQJWKH,QWHJUDWHG,2RIWKH&38
&38,)0
The following addresses are assigned to the integrated I/O of CPU 312 IFM:
Table 8-1 Integrate inputs and outputs on the CPU 312 IFM
,QSXWV2XWSXWV $GGUHVVHV 5HPDUNV
10 digital inputs 124.0 to 125.1
of those are 4 Inputs for
integrated functions:
124.6 to 125.1
Optional utilization of Inputs for
integrated functions:
• Counting
• Frequency measurement
• Interrupt input
See
,QWHJUDWHG)XQFWLRQs manual
6 digital outputs 124.0 to 124.5 –