S7-300 Automation System, Hardware and Installation: CPU 312IFM - 318-2 DP
A5E00203919-01
9-27
&RPPLVVLRQLQJWKH&38DV'3VODYH
5HTXLUHPHQWVIRUFRPPLVVLRQLQJ
• The DP master is configured and programmed.
• If the MPI/DP interface of CPU 318-2 DP is to be operated as DP interface, you
must configure the interface accordingly.
• You must program and configure CPU 31x-2 DP as a DP slave prior to
commissioning. That is, in 67(3 you must:
– "switch on" the CPU as DP slave,
– assign a PROFIBUS address to the CPU,
– assign a slave diagnostic address to the CPU,
– specify whether the DP master is an S7 DP master or another DP master,
– specify the address areas for data exchange with the DP master.
• All other DP slaves are programmed and configured.
*6'ILOHV
When working on an IM 308-C or non-Siemens system, you require a device
database (GSD) file to be able to configure CPU 31x-2 DP as a DP slave in a DP
master system.
&20352),%86 as of V 4.0 includes this GSD file.
When working with an older version or another configuration tool, you can
download the GSD file at:
• Internet URL http://www.ad.siemens.de/csi/gsd
or
• via modem from the 66&(Interface &HQWHU Fürth, Germany; Phone number
(0911) 911/737972
.
&RQILJXUDWLRQDQGSDUDPHWHUDVVLJQPHQWPHVVDJHIUDPH
67(3 supports you in configuring/programming CPU 31x-2 DP. Should you
require a description of the configuration and parameter assignment frame, in order
to use a bus monitor for example, you can find it on the Internet at
http://www.ad.siemens.de/csinfo under article ID 1452338.