&RQILJXULQJ
S7-300 Automation System, Hardware and Installation: CPU 312IFM - 318-2 DP
5-22 A5E00203919-01
If the jumper is not installed, the reference potential of the S7-300 is connected
internally to the ground conductor via an RC system and the rail. This discharges
radio-frequency interference current and avoids static charge.
1RWH
To create a floating reference potential, remove the jumper from the CPU between
the M terminals and functional ground.
 ,VRODWHGRUQRQLVRODWHGPRGXOHV
,VRODWHGPRGXOHV
In configurations with isolated modules, the reference potentials of the control
circuit (M
internal
) and the load circuit (M
external
) are galvanically isolated.
$SSOLFDWLRQUDQJHIRULVRODWHGPRGXOHV
Use isolated modules for:
All AC load circuits
DC load circuits with a separate reference potential, for example:
DC load circuits whose sensors have different reference potentials (for
example if grounded sensors are located at some considerable distance
from the control system and no equipotential bonding is possible)
DC load circuits with grounded positive pole (L+) (battery circuits).
,VRODWHGPRGXOHVDQGJURXQGLQJFRQFHSW
You can use isolated modules, regardless of whether or not the control system's
reference potential is grounded.