S7-300 Automation System, Hardware and Installation: CPU 312IFM - 318-2 DP
A5E00203919-01
5-49
,QIRUPDWLRQRQURXWLQJFDQEHIRXQGLQWKH
&38'DWD&38,)0±'35HIHUHQFH0DQXDO
In the &RPPXQLFDWLRQZLWK6,0$7,& manual.
([DPSOH7HUPLQDWLQJUHVLVWRULQWKH03,VXEQHW
The following figure shows you where to connect the terminating resistors on the
MPI subnet . In this example, the programming device (PG) is connected by
means of a stub cable only during commissioning or servicing .
OP 27
PG
PG
RS 485-
Repeater
1
CPU
PS
ET 200 M
S7-300
CPU
PS
CPU
CPU
PS
ET 200 M
S7-300
CPU
PS
CPU
CPU
PS
ET 200 M
S7-300
CPU
PS
CPU
OP 27
CPU
PS
ET 200 M
S7-300
CPU
PS
CPU
1
1
2
1
Installing Figure 5-19 the terminating resistors in an MPI subnet
.H\WRQXPEHUVLQWKHILJXUH
 Terminating resistor inserted
 PG connected by means of a stub cable for maintenance purposes
:DUQLQJ
Disturbance of data traffic might occur on the bus.
A bus segment must always be terminated at both ends with the terminating
resistor. This, for example, is not the case if the last slave with bus connector is off
power.
Since the bus connector draws its power from the station, the terminating resistor
has no effect.
Please make sure that power is always supplied to stations on which the
terminating resistor is active.
As an alternative, you can also use the PROFIBUS Terminator as active bus
termination.