3.2 Network topologies
SCALANCE X-400
24 Operating Instructions, 06/2015, C79000-G8976-C186-12
An interruption of the ring can be caused by loss of the connection between two devices or
by failure of a device in the ring.
If the test frames of the redundancy manager no longer arrive at the other ring port because
of an interruption in the ring, the redundancy manager connects its two ring ports. This
substitute path once again restores a functioning connection between all remaining devices
in the form of a linear bus topology.
As soon as the interruption is eliminated, the original transmission paths are established
again, the two ring ports of the redundancy manager are disconnected and the redundancy
clients informed of the change. The redundancy clients then use the new paths to the other
devices.
The time between the ring interruption and restoration of a functional linear topology is
known as the reconfiguration time.
If the redundancy manager fails, the ring becomes a functional linear bus.
Media redundancy methods
The following media redundancy methods are supported by SIMATIC NET products:
HRP (High Speed Redundancy Protocol)
Reconfiguration time: 0.3 seconds
MRP (Media Redundancy Protocol)
Reconfiguration time: 0.2 seconds
The mechanisms of these methods are similar. HRP and MRP cannot be used in the ring at
the same time.

Table of Contents

Other manuals for Siemens SCALANCE X-400

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SCALANCE X-400 and is the answer not in the manual?

Siemens SCALANCE X-400 Specifications

General IconGeneral
BrandSiemens
ModelSCALANCE X-400
CategorySwitch
LanguageEnglish

Related product manuals