3VL IEC molded case circuit breakers
System Manual, 11/2013, 110 0110 - 02 DS 03
129
Technical data
11
11.1
General data - 3VL molded case circuit breakers
Type
VL160X
3VL1
VL160
3VL2
VL250
3VL3
VL400
3VL4
VL630
3VL5
VL800
3VL6
VL1250
3VL7
VL1600
3VL8
Max. rated current I
n
[A]
160
160
250
400
630
800
1250
1600
N pole [A]
160
160
250
400
630
800
1250
1600
Rated insulation voltage U
i
in accordance with IEC 60947-2
Main current paths [V AC]
800
800
800
800
800
800
800
800
Auxiliary circuits [V AC]
690
690
690
690
690
690
690
690
Rated impulse withstand voltage U
imp
Main current paths [kV]
8
8
8
8
8
8
8
8
Auxiliary circuits [kV]
4
4
4
4
4
4
4
4
Rated operating voltage U
e
IEC 50 / 60 Hz [V AC]
690
4)
690
690
690
690
690
690
690
IEC DC
3)
500
600
600
600
600
-
1)
-
1)
-
1)
NEMA 60 Hz [V AC]
600
600
600
600
600
600
600
600
Utilization category
(IEC 60947-2)
A A A A A A A A
Permissible ambient temperature
Operation [°C]
2)
0 to
+70
-25 to
+70
-25 to
+70
-25 to
+70
-25 to
+70
-25 to
+70
-25 to
+70
-25 to
+70
Storage [°C] -40 to
+80
-40 to
+80
-40 to
+80
-40 to
+80
-40 to
+80
-40 to
+80
-40 to
+80
-40 to
+80
1) Breaker cannot be used for direct current.
2) Exception: 3VL molded case circuit breaker w
ith TMTU: 0 °C ... 70 °C
3) The values apply for at least 3 current paths in series and extremely high breaking capacity L. For switching direct
current, the maximum permissible direct voltage per current path must be observed.
4) VL160X in the 16 A and 20 A version cannot be used at 690 V.
Note
For more information, see the following chapter:
Use in DC systems
(Page 60) under "Suggested circuits for DC networks"