Technical data
11.5 Power loss
3VL IEC molded case circuit breakers
150 System Manual, 11/2013, 110 0110 - 02 DS 03
11.5
Power loss
Power loss for fixed-mounted molded case circuit breakers
Thermal-magnetic overcurrent releases (TM)
The table below shows the
power loss and the current path resistance for thermal-magnetic
overcurrent releases (TM)
. The power loss applies for I
n
with 3-phase balanced load. The
specified power loss is the sum of all current paths. The current path resistance is only a
guide value and can fluctuate.
Table 11- 24 Power loss for thermal-magnetic overcurrent releases (TM)
Type
Rated current [A]
Power loss [W]
Path resistance [mΩ]
VL160X
16
11
14
20
17
14
25
7
3,7
32
11
3,6
40
16
3,3
50
15
2,0
63
18
1,5
80
24
1,3
100
22
0.73
125
31
0,66
160
41
0,53
VL160
50
16
2,1
63
21
1,8
80
27
1,4
100
27
0,90
125
36
0,77
160 55 0,63
VL250
200
60
0,47
250 71 0,38
VL400
200
60
0,50
250
84
0,45
315
120
0,40
400
175
0,36
VL630
315
85
0,29
400
120
0,25
500
170
0,23
630
230
0,19