3VL IEC molded case circuit breakers
System Manual, 11/2013, 110 0110 - 02 DS 03
89
Connecting
7
7.1
Cables and busbars
The 3VL molded case circuit breaker can be connected using cables, flexible copper bars or
busbars.
Thermal and electrodynamic stresses affect these conductors in the event of a short-circuit.
To avoid dangerous effects, it is necessary to asses them correctly and to take appropriate
measures to suppress them.
The diagrams and tables below show the recommended maximum clearance between the
molded case circuit breaker and the first point.
Overview of cable and busbar mounting methods
Cable mounting
Busbar mounting
Table 7- 1 Recommended cable mounting clearances
VL160X
VL160
VL250
VL400
VL630
VL800
VL1250
VL1600
A cable mm
100
100
130
150
300
B cable mm
400
400
400
400
600
C bar mm
250
This table applies for all switching capacities.