Application planning   
5.6 Use in motor protection 
  3VL IEC molded case circuit breakers 
64  System Manual, 11/2013, 110 0110 - 02 DS 03 
 
The overload and short-circuit releases are designed for optimal protection and direct 
starting of three-phase AC squirrel-cage motors. The molded case circuit breakers for motor 
protection are sensitive for phase failures and have an adjustable trip class. 
The ETUs operate with a microprocessor. 
 
reakers with motor protection function are suitable for use in IE2 motors. 
You can obtain detailed information for the use of the 3VL molded case circuit breaker with 
IE3 motors on request.
 
Operating principle of the overcurrent releases 
The tripping characteristic curves of the inverse-time delayed overload releases are specially 
designed for overload protection of 3-phase AC motors. 
With the inverse-time delayed overload release "L", the value I
R
 can be set to be 0.4 to 1.0 
times the rated current I
n
 of the molded case circuit breaker. This occurs in 0.01 increments 
(e.g. 0.40 / 0.41 / 0.42 ... 0.99 / 1.0 x I
n
), so that the molded case circuit breaker exactly 
matches the rated current of the motor to provide optimal protection. 
The current transformers in the 3VL molded case circuit breaker not only measure the load 
current, they also supply power to the electronic trip unit. No external auxiliary power supply 
is required.  
This independence from an external energy supply guarantees a high standard of safety. 
Machine tools, manufacturing systems, presses, fans, air-conditioning units and packaging 
machines all require motors that must be protected. This is the main area of application of 
the 3VL molded case circuit breakers for motor protection. 
The 3VL molded case circuit breakers offer the option of selecting from various trip units with 
fixed or adjustable trip classes that are suitable for differing motor applications. 
This version is equipped with a thermal image, phase failure sensitivity and the fixed trip 
class 10. 
This version is equipped with an adjustable trip class 10 to class 30 in addition to the thermal 
image and phase failure sensitivity.