Installing/mounting
6.2 Mounting and safety clearances
3VL IEC molded case circuit breakers
80 System Manual, 11/2013, 110 0110 - 02 DS 03
6.2
Mounting and safety clearances
Permissible mounting positions
All 3VL molded case circuit breakers can be mounted in the positions shown:
Unlimited:
There is a separate mounting assembly for VL800 to VL1600 molded case
circuit breakers with guide frame in lateral installation position.
Limited:
Use of the internal accessories possible
Permissible current load factor 0.9
Not allowed: motorized operating mechanisms, rotary operating
mechanisms, plug-in assembly / withdrawable assembly
Safety clearances
During a short-circuit interruption, high temperatures, ionized gases and high pressures
occur in and above the arcing chambers of the molded case circuit breaker.
Safety clearances are required to:
allow pressure distribution
prevent fire or damage caused by any diffused ionized gases
prevent a short circuit to grounded parts
prevent arcing or short-circuit currents to live sections