Installing/mounting
6.2 Mounting and safety clearances
3VL IEC molded case circuit breakers
System Manual, 11/2013, 110 0110 - 02 DS 03
81
Table 6- 2 Permissible safety clearances in accordance with IEC 60947
Molded
case circuit
breaker
type
dard
Figure 6-1 Safety clearances
Figure 6-2 No minimum clearance between two horizontally or vertically installed molded case
circuit breakers
Table 6- 3 Definition of the permissible safety clearances in [mm] between
A:
Molded case circuit breakers and busbars (uninsulated and grounded metal); terminal cover
required above 600 V AC, 500 V DC
Molded case circuit breaker terminal and lower panel
C: Sides of the molded case circuit breaker and side panels left / right (uninsulated and grounded
D: Molded case circuit breaker and non-conductive parts with at least 3 mm thick insulation
(insulator, insulated bar, painted plate)