Technical data
11.2 Technical overview
3VL IEC molded case circuit breakers
134 System Manual, 11/2013, 110 0110 - 02 DS 03
High breaking capacity VL160X, VL160 to VL400
Table 11- 5 SENTRON VL - H rated breaking current (kA) symmetrical (high breaking capacity)
IEC 60947-2 Up to 240 V AC
Up to 415 V AC
Up to 440 V AC
Up to 500/525 V AC
100/75
70/70
42/32
30/23
1)
100/75
70/70
50/38
40/30
100/75
70/70
50/38
40/30
100/75
70/70
50/38
40/30
Up to 250 V DC
Up to 500 V DC
30/30
30/30
32/32
32/32
32/32
32/32
32/32
32/32
1)
For rated currents from 25 A. VL160X in the 16 A and 20 A version cannot be used at 690 V.
High breaking capacity VL630 to VL1600
Table 11- 6 SENTRON VL - H rated breaking current (kA) symmetrical (high breaking capacity)
IEC 60947-2 Up to 240 V AC
Up to 415 V AC
Up to 440 V AC
Up to 500/525 V AC
100/75
70/70
50/38
40/30
100/75
70/70
50/38
40/30
100/50
70/35
50/38
40/30
100/50
70/35
50/38
40/30
Up to 250 V DC
Up to 500 V DC
30/30
30/30
--
--
--
--
--
--